Commercial battery storage fire safety: the UK standards

Which regulations and standards apply to a battery on a business site, and what each one covers. An independent guide, updated for the BS 7671 changes in 2026. This site is not an installer.

Fire is the concern most likely to stall a commercial battery project, and much of the advice in circulation is written for homes. This page sets out the documents that actually govern a battery on a commercial or industrial site, what each one covers, and what to ask for at each stage. It explains standards; it does not replace a designer's or fire engineer's judgement for your site.

The standards map

Each row is a different job: the electrical installation, the equipment, the premises, the planning stage, and the insurance. A compliant project needs all of them, not one.

DocumentWhat it coversFor a commercial battery?Status
BS 7671 Chapter 57 Electrical installation of stationary secondary batteries whose purpose is to store and supply electricity Yes: the wiring regulations for the installation Added by Amendment 4:2026 (published 15 Apr 2026); previous edition withdrawn 15 Oct 2026
IET Code of Practice for Electrical Energy Storage Systems Specifying, designing, installing, commissioning, operating and maintaining electrochemical storage in low-voltage installations Yes: covers dwellings, commercial and industrial applications 3rd edition, 2024
BS EN IEC 62933-5-2 Safety requirements for grid-integrated energy storage systems that use electrochemical (battery) storage Yes: ask for evidence the system conforms BS EN IEC 62933-5-2:2020; IEC published a second edition in December 2025
IEC 62619 Safety requirements for secondary lithium cells and batteries in industrial applications, including stationary storage Yes: the cells and battery modules IEC 62619:2022 (2nd edition)
PAS 63100:2024 Fire protection of battery systems in dwellings (up to 200 m² floor area) No: dwellings only (see PAS 63100 explained) Published 20 Mar 2024
NFCC grid-scale guidance Planning-stage guidance for fire and rescue services on open-air lithium systems of 1 MWh or more Yes, for larger containerised sites Approved December 2025, replacing the 2023 guidance
Fire safety law (England & Wales, Scotland) The responsible person for non-domestic premises must assess and manage fire risk Yes: the battery belongs in the fire risk assessment In force
Your insurer Conditions on siting, separation, detection or suppression, and evidence from the manufacturer Yes: often the deciding factor in practice Ask before you order plant
MCS MIS 3012 MCS battery installation standard for certified installers Only small systems: it covers installations up to 50 kW MIS 3012:2025

Grid connection (G98, G99, G100) is a separate set of rules, covered in the G99 timeline guide and the G100 guide.

What changed in 2026: BS 7671 Chapter 57

Until 2026 the Wiring Regulations dealt with batteries in a short group of regulations (551.8). BS 7671:2018+A4:2026, published on 15 April 2026, moved those requirements into a new Chapter 57, "Stationary secondary battery installations": the first chapter of BS 7671 written for battery storage. According to the IET's guidance on the amendment, it applies where the battery's designed purpose is to store and supply electricity to the installation, and it excludes batteries built into products covered by their own product standards, such as pluggable UPS units and emergency lighting.

The previous version of BS 7671 is withdrawn on 15 October 2026. Any commercial battery designed now should be designed to the amended standard, and it is reasonable to ask an installer to confirm that in writing. For dwellings, the IET's guidance says Chapter 57 requires batteries to be installed in accordance with PAS 63100 (regulation 570.6.7.203). For other premises PAS 63100 does not apply directly; the location and fire protection are decided through the fire risk assessment and the other references on this page.

PAS 63100 is for homes, not commercial sites

PAS 63100:2024 is BSI's specification for protection against fire of battery systems for use in dwellings, limited to dwellings of up to 200 m² floor area. It is quoted on many commercial battery websites (this one included, until it was corrected in September 2026), but its own title rules out a factory, warehouse or office. In 2024 MCS noted that PAS 63100 had no standing in UK regulations; since Amendment 4:2026, BS 7671 itself calls it up, for batteries in dwellings. If a commercial proposal names PAS 63100 as its fire standard, ask which commercial references the design actually follows. More in PAS 63100 explained.

Larger sites: the NFCC guidance

The National Fire Chiefs Council's guidance for fire and rescue services was approved in December 2025 and replaces the 2023 version. It applies to battery systems deployed in the open air with an energy capacity of 1 MWh or more using lithium batteries, which takes in many containerised commercial installations. Two of its figures shape site layouts:

  • an initial minimum distance of 30 m between battery cabinets (or associated transformers and switchgear) and occupied buildings, before mitigation such as blast walls is considered;
  • fire hydrants that achieve a flow rate of no less than 25 litres per second.

It is written for fire and rescue services responding to planning consultations, so on a larger site it is worth talking to the local fire and rescue service early; for 1 MWh or more, planning guidance in England encourages exactly that (see battery storage planning permission). On a constrained yard, the separation requirement can decide between a container and an indoor system, so it belongs at feasibility stage, not after the order.

The fire risk assessment, and siting

The person responsible for fire safety in non-domestic premises must assess fire risk (the Regulatory Reform (Fire Safety) Order 2005 in England and Wales, the Fire (Scotland) Act 2005 in Scotland). A battery changes that risk, so the assessment should be reviewed before installation. The questions it has to answer differ by install type:

  • Containerised, outdoors: separation from buildings, boundaries and escape routes; firefighting access and water; detection and, where required, deflagration venting. The advantage is that a thermal event stays outside the occupied building. See containerised installation.
  • Indoor cabinet: the room is the fire barrier, so compartmentation to the building fire strategy, ventilation for cooling and any off-gassing, and detection tied into the building alarm. See indoor cabinet installation.

Lithium-iron-phosphate (LFP) cells are generally regarded as more thermally stable than NMC chemistry, which is one reason they are the usual choice for stationary storage, but chemistry does not replace siting and detection.

What your insurer will ask

Insurers set their own conditions, and they are often the practical deciding factor. Expect questions about the chemistry, the manufacturer's test evidence, the separation from other buildings and stock, detection and any suppression, the monitoring arrangements, and who maintains the system. Share the fire risk assessment and the installer's design with your insurer before plant is ordered: a condition that arrives after installation can be expensive to meet.

Questions to ask an installer about fire safety

  • Is the installation designed to BS 7671 as amended by A4:2026, including Chapter 57?
  • Which parts of the IET Code of Practice does the design follow, and who signs the design off?
  • Can you show conformity evidence for BS EN IEC 62933-5-2 and IEC 62619 for this exact product?
  • If PAS 63100 is cited, why, given that it covers dwellings?
  • For 1 MWh or more in the open air, how does the layout compare with the NFCC guidance, and has the fire and rescue service been consulted?
  • Has the insurer seen the design, and what did they ask for?
  • How will the fire detection and any suppression be proved at commissioning, and which records will you hand over?

The installer checklist covers the rest: registration, grid-connection experience, insurance and warranties.

Request quotes from installers who design to these standards

Free and no obligation. This site is not an installer.

  • 1. Tell us about the site: what you want the battery to do, your supply, and any half-hourly data you have.
  • 2. Your enquiry is passed to installers who cover your area. This site is not one of them and takes no part in the work.
  • 3. Compare what comes back against the installer checklist before you commit to a survey.

By sending this you agree to the privacy notice, which explains that your enquiry is passed to third-party installers. It is not sold to anyone else.

Fire safety questions

What are the regulations for battery storage in the UK?

For a commercial battery, the electrical installation falls under BS 7671, which gained a dedicated chapter for stationary batteries (Chapter 57) in Amendment 4:2026. The IET Code of Practice for Electrical Energy Storage Systems is the main design reference, the equipment should meet BS EN IEC 62933-5-2 and IEC 62619, the premises need a fire risk assessment under fire safety law, fire and rescue services use NFCC guidance for open-air sites of 1 MWh or more, and your insurer will add its own requirements. The grid connection is covered separately by G98 or G99.

Does PAS 63100 apply to commercial battery storage?

No. PAS 63100:2024 is BSI's specification for fire protection of battery systems in dwellings (up to 200 m² of floor area). Under BS 7671 Amendment 4:2026 it applies to batteries in dwellings; for commercial premises the location and fire protection come from the fire risk assessment, the IET Code of Practice and the insurer's requirements.

What is BS 7671 Chapter 57?

Chapter 57, "Stationary secondary battery installations", was added to the IET Wiring Regulations by Amendment 4:2026, published on 15 April 2026. It is the first chapter of BS 7671 dedicated to battery storage and replaces the old regulation group 551.8. The previous version of BS 7671 is withdrawn on 15 October 2026, so new battery installations should be designed to the amended standard.

Do I need a fire risk assessment for a commercial battery?

Your premises already need one: in England and Wales the Regulatory Reform (Fire Safety) Order 2005, and in Scotland the Fire (Scotland) Act 2005, require the person responsible for non-domestic premises to assess fire risk. Adding a battery changes that risk, so the assessment should be reviewed to cover the battery's location, detection, access and the effect of a battery fire on escape routes.

How far must a battery container be from buildings?

There is no single UK figure for every site. For open-air lithium systems of 1 MWh or more, the NFCC guidance for fire and rescue services proposes an initial minimum distance of 30 m between battery cabinets (or associated transformers and switchgear) and occupied buildings, before mitigation such as blast walls is considered. Smaller systems are sited through the fire risk assessment, the manufacturer's installation instructions and the insurer's requirements.

Does a commercial battery installer need MCS certification?

Usually not for the battery. MCS's battery installation standard (MIS 3012) covers installations up to 50 kW, so most commercial systems are outside its scope. For larger systems, check competent-person registration for the electrical work, the installer's G99 track record, and evidence that the design follows BS 7671 Chapter 57 and the IET Code of Practice.

Sources

Checked 29 September 2026. Standards change: confirm the current edition with the issuing body before relying on it.